NI Electrical Revision Reference

Northern Ireland · BS 7671 recap
NI Electrical Revision Reference
Compact UK/Northern Ireland electrical revision notes for competent-person learning and recap.
Revision app scope
This is a revision/reference aid for competent persons, apprentices, improvers and qualified electrical workers. It is not a public DIY wiring guide and it does not replace BS 7671, supervision, manufacturer instructions, employer procedures or site-specific judgement.
Safe isolation
Life-critical isolation principles and common mistakes.
Start here
Circuit concepts
Lighting, sockets, rings, radials and high-load circuits.
Circuits
Cable design
Current-carrying capacity, voltage drop, grouping and diversity.
Design
Inspection & testing
What tests prove and how documents relate.
Testing
EICR testing
Condition reports, coding, diagrams, checklists and NI landlord context.
New module
Earthing & bonding
Supply types, MET, CPC and protective bonding recap.
PME / TT / TN
NI compliance
Part P correction, Building Control context and workplace notes.
NI-specific
EV charging
Open-PEN, PME, load assessment and NIE notification recap.
Review needed
Sources & review
Official links and manual review checklist.
Modal
Safety boundary
Deep technical revision is useful, but the final decision for any design, installation, inspection, testing or certification task must be checked against current standards, site conditions and competent judgement.
Scope & safety
What this app is for, and what it cannot replace.
Boundary
Competence first
Only carry out electrical work you are competent, authorised and equipped to do.
Review point
Current standard
BS 7671 changes over time. Treat edition references as review points.
Use
Revision, not instruction
These notes explain concepts and checks. They do not replace project-specific work.
Risk
Shock, burns, fire
Incorrect work can cause electric shock, burns, fire, injury or death.
How to use it
Use topic cards, tables and glossary terms to refresh concepts before study, supervised work, inspection discussion or documentation review.
Source and update policy
Standards and Northern Ireland legal duties change, so review status stays visible.
Review policy
Any section involving BS 7671, NI tenancy law, Building Control, EV charging, alarms, inspection/testing, special locations, earthing or bonding should be reviewed before publication and periodically after.
AreaReview sourceWhy
BS 7671IET/BSI current edition informationEdition and amendment references can change.
NI domestic complianceElectrical Safety First and official NI sourcesDo not import England/Wales Part P assumptions into NI.
Private tenancy dutiesDepartment for Communities NIDates, report duties and alarm requirements are legal/current-state content.
EV chargingConsumer Council NI and NIE NetworksNotification and network process wording can change.
BS 7671 current-edition note
Use edition wording as a review point, not as a design answer.

BS 7671 is updated by amendments. As of 2026, BS 7671:2018+A4:2026 has been published. During the transition period, the previous edition remains valid until 15 October 2026. After transition, check the latest IET/BSI position before relying on edition wording.

Do not hard-code design answers
For design, installation, inspection and testing decisions, check the current standard, manufacturer instructions and project documentation.
Safe isolation
Safe isolation prevents dangerous voltage being present at the point of work.
Identify
Correct circuit, equipment and possible sources.
Isolate
Remove supply and consider alternative feeds.
Secure
Prevent unintended re-energisation.
Verify
Prove dead at the work point with suitable equipment.
What it proves
Correct circuit dead
The circuit/equipment is identified, isolated, secure and proved dead.
Test equipment
Known working
Voltage indicator proving before and after is a key principle.
PrincipleRevision note
IdentifyConfirm the correct circuit/equipment. Labels and colours are not enough.
IsolateConsider all relevant live conductors, supplies and alternative sources.
SecurePrevent re-energisation using lock-off/warning methods where appropriate.
Prove deadTest at the point of work with suitable equipment and procedure.
Common mistakes
Switching off a light switch, trusting labels, relying on conductor colours, missing borrowed/shared neutrals, missing backfeeds, not locking off, or testing the wrong point.
Shock, fire and ADS principles
Core concepts that sit behind circuit design, verification and fault finding.
Fault occursLine-to-exposed-part fault creates dangerous touch voltage risk.
Fault pathCPC, earthing and bonding influence current path and impedance.
Device responseProtective device operation depends on current and characteristics.
DisconnectionSupply is disconnected within required conditions when design is valid.
VerificationInspection and testing provide evidence, not assumptions.
Shock
Basic, fault, additional
Barriers, enclosures, insulation, ADS and RCD/RCBO roles.
Fire
Heat and faults
Overload, short circuit, loose connections, arcing and environmental conditions.
Fault path
Line to CPC
Earth fault loop path, transformer return path, CPC continuity and bonding.
ADS
Disconnection
Zs and protective-device characteristics matter; verification is required.
Common mistake
Do not assume an RCD makes any poor circuit safe. RCD/RCBO protection has specific purposes and limitations.
Glossary
Compact definitions for common revision terms.
TermMeaning
BS 7671UK standard for electrical installations, published with amendments.
Competent/skilled personPerson with sufficient knowledge, training, experience and judgement for the task and risk.
Line / neutral / CPCLine is live conductor, neutral is return conductor, CPC is circuit protective conductor.
METMain earthing terminal for earthing, bonding and protective conductors as applicable.
ADSAutomatic disconnection of supply under required fault conditions.
RCD / RCCB / RCBOResidual current devices; RCBO combines residual current and overcurrent protection.
MCB / SPD / AFDDOvercurrent device, surge protective device and arc fault detection device.
Zs / Ze / R1+R2Earth fault loop impedance terms used in fault path and verification work.
EIC / MEIWC / EICRInstallation certificate, minor works certificate and condition report.
PME / TN-S / TN-C-S / TTSupply earthing concepts. Confirm the actual arrangement on site.
Circuit concepts
Lighting, switching, socket circuits, ring finals, radials and dedicated loads.
SupplyActual source and earthing arrangement must be confirmed.
ProtectionDevice selection links to load, cable, route and fault conditions.
Wiring methodRoute, grouping, heat and mechanical risk affect design.
LoadEquipment use, demand and manufacturer data shape the final design.
EvidenceInspection, testing and certification record the outcome.

Lighting circuits may contain permanent line, switched line, neutral and CPC conductors depending on wiring method. Older installations, alterations and different methods can make conductor identification unreliable by colour alone.

  • permanent line and switched line
  • neutral at switch vs neutral at light
  • CPC continuity
  • borrowed/shared neutrals risk
  • two-way/intermediate switching concept
  • smart controls and neutral requirement
  • SELV/driver considerations for LED lighting

Socket-outlet circuits may be radial or ring final circuits. The arrangement, protective device, cable route, loading, RCD/RCBO protection and test results must all be considered.

  • radial concept
  • ring final concept
  • unfused spur concept
  • fused connection unit concept
  • load distribution
  • continuity of line, neutral and CPC
  • ring final testing purpose
  • limitations of visual inspection alone

High-load or fixed equipment circuits require design around the actual load, manufacturer instructions, cable route, installation method, grouping, thermal insulation, voltage drop, protection, isolation and certification.

  • cooker, hob or oven
  • electric shower
  • immersion heater
  • EV charger
  • heat pump
  • outbuilding supply
  • workshop equipment
Cable and design concepts
Design factors, current-carrying capacity, voltage drop, Zs, diversity and thermal effects.
Concept
Current-carrying capacity
Not one fixed number; route, heat, grouping and environment matter.
Formula
Voltage drop
Use as revision formula only. Confirm values and limits.
Fault path
Zs & disconnection
Loop impedance affects protective device operation.
Load
Diversity
Assessment of likely simultaneous load, not a guess.
Vd = (mV/A/m x Ib x length) / 1000
Selection factorRevision note
Design current and future loadKnow the actual load and realistic use case.
Installation method and groupingHeat dissipation affects usable capacity.
Voltage drop and ZsLength and impedance affect performance and disconnection.
Mechanical/environmental conditionsRoute, protection and surroundings matter.
Manufacturer instructionsEquipment requirements are part of design context.
Consumer units and protective devices
Roles and limitations of common protective devices.
MCB
Overcurrent
Overload and short-circuit protection within device characteristics.
RCD / RCCB
Residual current
Detects imbalance; does not provide overload protection by itself.
RCBO
Combined device
Overcurrent and residual current protection for one circuit.
SPD / AFDD
Surge and arc faults
Selection depends on current BS 7671, risk and installation context.
Schedules and labels
Clear circuit identification, accurate schedules, test documentation and spare-way records support safe operation and future work.
Earthing, bonding and supply types
Earthing provides a fault path; bonding reduces dangerous potential differences.
Supply typeBasic conceptCautions
TN-SSeparate supply neutral and earth paths from source.Confirm actual supply; do not assume from appearance.
TN-C-S / PMENeutral and earth combined in part of supply, separated at installation.EV, outbuildings and special cases need care.
TTInstallation uses local earth electrode for earthing.Electrode resistance, RCDs, testing and maintenance matter.
Earthing
Fault current path
Supports operation of protective devices when correctly designed.
Bonding
Potential difference
Not the same thing as earthing.
CPC
Continuity matters
Part of the fault path and must be verified.
PME caution
Design-dependent
Avoid blanket always/never statements for EV and outbuildings.
Kitchens and high-load equipment
Fixed and high-load equipment requires design around the real load and installation context.
  • cooker, hob and oven loads
  • washing machine, dryer and dishwasher loads
  • boiler and controls
  • extraction and lighting
  • boiling-water taps
  • dedicated circuits vs shared circuits
  • isolation and accessibility
  • manufacturer instructions
Design-dependent
Circuit design needs attention to load, diversity, appliance instructions, isolation, cable route, thermal effects, RCD/RCBO protection, socket positions, water/heat, accessibility and future use.
Inspection and testing
Revision of what tests are for and what results relate to.
Inspect
Look for suitability, damage, access, identification and workmanship.
Dead tests
Check continuity, insulation and polarity foundations.
Live tests
Confirm fault path, PFC and device behaviour where applicable.
Record
Document results, observations, limitations and outcome.
Dead test
Continuity
CPC/bonding continuity and ring final continuity purposes.
Dead test
Insulation resistance
Checks insulation condition between conductors.
Verification
Polarity
Correct conductor arrangement and switching/protection in line.
Fault
Loop & PFC
Loop impedance and prospective fault current relate to disconnection and breaking capacity.
Competence boundary
This is not a substitute for Guidance Note 3, current BS 7671, calibrated instruments, supervision or competence.
Certificates and EICR coding
Document purpose and condition report coding recap.
DocumentUsed forRevision notes
EICNew installation, rewire, new circuits or significant work.Records design, construction, inspection and testing responsibility.
MEIWCCertain minor additions or alterations without a new circuit.Not for every job; check scope.
EICRCondition report for an existing installation.Records observations, codes and overall assessment; not a certificate for new work.
CodeMeaningRevision note
C1Danger present.Immediate action required.
C2Potentially dangerous.Urgent remedial action required.
C3Improvement recommended.Not normally unsatisfactory by itself.
FIFurther investigation required.Needs investigation without delay.
LIMLimitation.Agreed limitation; must not hide accessible defects.
EICR Testing Reference
Dense competent-person reference for Electrical Installation Condition Reports, Northern Ireland tenancy context, coding, inspection, testing and report writing.

Competent-person reference only. This section is for electrical learning, revision and professional reference. It is not a substitute for BS 7671, IET Guidance Note 3, manufacturer instructions, risk assessment, safe systems of work, insurance conditions or competent supervision.

Apprentice note. If you are in training, do not carry out EICR work unsupervised unless you are competent and authorised to do so. Use this section to understand the process, terminology, observations and report structure, then verify everything against current standards and supervisor instructions.

Regulation note. Standards, model forms and legal duties can change. Verify current requirements against the applicable version of BS 7671, current IET guidance, Electrical Safety First guidance, current Northern Ireland Department for Communities guidance, manufacturer information and local procedures.

Original summary wordingNo invented valuesVerify current source

An Electrical Installation Condition Report records the condition of an existing electrical installation within agreed extent and limitations. It is a structured inspection and testing report, not a design certificate for new work and not a quote for remedial work.

What it is

A report on whether an existing installation is satisfactory for continued service, based on inspection, testing, observations, limitations and competent judgement.

What it is not

It is not an Electrical Installation Certificate, not a Minor Works Certificate, not a consumer-unit replacement certificate and not proof that future alterations are safe.

Who carries it out

A competent and authorised person with suitable inspection/testing knowledge, experience, equipment, calibration arrangements, insurance and safe systems of work.

Old installations

Older work is assessed against current safety expectations, but age alone does not make an installation unsafe. Coding depends on risk, condition and context.

DocumentPurposeTypical use
EICRCondition report for an existing installation.Periodic inspection, landlord checks, sale/purchase condition review, workplace maintenance.
EICCertificate for new installation work.New installation, rewire, new circuit or major alteration requiring design/construction verification.
MEIWCCertificate for certain minor electrical installation work.Limited additions or alterations where no new circuit is installed and the certificate scope is appropriate.
NI private tenancy context
Private landlords in Northern Ireland must have the hardwired electrical installation inspected and tested at least every 5 years by a qualified person, or sooner if the report requires it. New private tenancies apply from 1 April 2025; existing tenancies granted before then must comply by 1 December 2025.
Full EICR workflow conceptScopeInspectTestCodeReportReview
Concept flow: enquiry, previous records, agreed scope, risk assessment, visual inspection, safe isolation, dead tests, live tests where justified, functional checks, coding, report completion and follow-up.
Agree
Client information, previous reports, extent, limitations, access and power interruption.
Assess
Risk assessment, supply/earthing, occupancy, multiple supplies and sensitive loads.
Inspect/test
Visual inspection, safe isolation, dead testing, live testing only where competent and justified.
Report
Codes, urgent danger communication, report issue, remedial work evidence and next inspection date.

Client questions

  • reason for report and property use
  • previous EIC/EICR/MEIWC availability
  • known faults or nuisance tripping
  • whether power can be interrupted

Installation clues

  • property age and occupancy
  • number of consumer units or DBs
  • likely supply/earthing type
  • outbuildings and external supplies

Special systems

  • PV, battery storage, generators or UPS
  • EV charging
  • immersion, shower, cooker and heating
  • alarms, data, security and ELV systems

Occupied property risk

  • vulnerable persons and medical equipment
  • fridges, freezers, IT equipment and alarms
  • pets and access to rooms, lofts or garages
  • tenant/landlord communication route

Core test kit

Multifunction tester, proving unit, two-pole voltage indicator or approved test lamp, GS38-compliant leads/probes, continuity leads and long lead/wander lead where appropriate.

Support kit

Lock-off kit, warning notices, labels, camera, notebook, forms/software, suitable hand tools, PPE and torque screwdriver where relevant.

Condition and calibration

Check instrument condition, lead condition, battery state, calibration status and suitability for the installation category before use.

Socket tester warning

Plug-in socket testers can indicate some issues but do not replace competent inspection, testing, safe isolation or calibrated instruments.

Competent-person only
Inspection and testing of live or potentially live installations must only be carried out by a competent and authorised person using suitable test equipment and safe working procedures.
Safe isolation sequence conceptIdentifyIsolateLock offProveVerify dead
Concept only: identify, inform, switch off, secure, post warning, prove tester, check relevant conductors, and re-prove tester under the applicable safe system of work.

Do not rely on neon screwdrivers, assumptions, labels, conductor colours or non-contact indicators as the primary method of proving dead. Watch for borrowed neutrals, multiple supplies, PV, battery storage, generators, UPS, heating/control circuits, smart controls, automatic switching and diverted neutral currents.

Intake and supply

  • service head, metering and isolator visual condition
  • main switch and tails visible condition
  • earthing arrangement indicators
  • supplier/distributor defects referred appropriately

Consumer unit

  • covers, blanks, barriers and IP suitability
  • signs of overheating, damage or loose equipment
  • RCD/RCBO/SPD/AFDD presence where relevant
  • accessibility, schedules and labels

Earthing and bonding

  • main earthing conductor and MET
  • main protective bonding to gas, water, oil, steel or other services where relevant
  • continuity and connection condition
  • extraneous-conductive-parts judgement

Circuits and accessories

  • cable condition, support and mechanical protection
  • safe zone awareness and damage signs
  • sockets, switches, accessories and evidence of poor alterations
  • lighting, downlights, showers, cookers, heating and outdoor equipment
TN-S earthing arrangement conceptSupplyMET
TN-S concept: separate neutral and earth paths from the source. Confirm the actual arrangement, Ze and bonding on site.
TN-C-S or PME earthing arrangement conceptSupplyMET
TN-C-S/PME concept: combined conductor in part of the supply, separated for installation use. EV and outbuilding decisions are context-dependent.
TT earthing arrangement conceptSupplyMET
TT concept: installation earth electrode. RCD dependence, electrode condition and testing/maintenance are central to judgement.
TypeRevision effectEICR caution
TN-SSeparate supply neutral and earth paths.Confirm by inspection/enquiry/testing; appearance alone can mislead.
TN-C-S / PMECombined supply conductor separated at the installation.Open-PEN risk awareness for EV, outbuildings and outdoor conductive parts.
TTLocal electrode provides installation earth reference.RCD effectiveness, electrode condition and bonding require careful review.
ITRare/special arrangement.Do not assume domestic TN/TT logic applies; check specialist design information.

Ring finals

Inspect accessories, spurs, load signs and continuity evidence. Common issues include broken ring conductors, borrowed/shared neutrals, damaged accessories and poor additions.

Radial sockets

Review route, load, RCD/RCBO protection, CPC continuity, polarity and outdoor-use implications.

Lighting

Check CPC presence, Class I fittings, downlight heat/fire issues, borrowed neutrals, switching and older colours.

High-load circuits

Cookers, showers, immersion heaters and heating circuits need review against load, isolation, route, protection and manufacturer data.

External/outbuilding

Consider mechanical protection, water ingress, glands, earthing/bonding, extraneous parts, future loads and PME/TT decisions.

Special interfaces

EV, PV, batteries, smoke/heat alarms and ELV/data separation need system-specific awareness and source checks.

Dead tests establish continuity, insulation condition, polarity foundations, circuit identity and protective conductor presence without energising test points. They are not a substitute for competence, calibrated equipment or current GN3/BS 7671 instructions.

Dead test purposeWhat it establishesCommon traps
CPC/bonding continuityProtective path and bonding connection continuity.Parallel paths, poor contact, wrong conductor or inaccessible points.
Ring final r1/rn/r2Continuity of line, neutral and CPC around the ring.Cross-connections, spurs mistaken for ring legs, loose terminals.
R1+R2Line-to-CPC continuity contribution to fault path.Borrowed neutrals, open CPCs, parallel earth paths.
Insulation resistanceCondition between conductors and circuits.Sensitive equipment, connected loads, SPDs, electronics and damp conditions.
Dead polarityLine conductor switching/protection and conductor identification.Assumptions from colour, older wiring and mixed-age alterations.
Ring final continuity conceptr1rnr2
Ring continuity concept for r1, rn and r2. Verify method and expected interpretation against current guidance.
Figure-of-eight cross-connection conceptcross-connection concept
Figure-of-eight concept used to expose ring continuity and polarity issues. This is not a test-lead placement diagram.
Radial R1 plus R2 conceptR1R2
Radial R1+R2 concept: line and CPC path relationship, subject to current procedure and limitations.
Insulation resistance conceptConductorConductor
Insulation resistance concept: checking insulation condition between conductors after suitable disconnection/precautions.
Main bonding continuity conceptMETService
Main bonding continuity concept between MET and incoming services where bonding is required.
Live testing warning
Live tests are competent-person-only work. They require suitable approved test equipment, safe systems of work, risk assessment and current guidance. This section explains purpose and risk, not public test steps.
Live testPurposeRisk/limitation
ZeExternal earth fault loop impedance at origin or by enquiry/measurement as appropriate.Requires care around supply equipment and live conditions; verify current method.
PFC/PEFC/PSCCProspective fault current values for breaking-capacity assessment.Supply conditions and measurement method affect result.
ZsEarth fault loop impedance at circuit points for disconnection assessment.No-trip tests have limitations; RCD support needs current guidance.
RCD/RCBO checksConfirms residual-current device function against relevant requirements.Type AC/A/F/B awareness, load effects and manufacturer data matter.
Functional/voltage/polarityConfirms operation, voltage presence and line/neutral arrangement.Can expose users and equipment to risk if poorly planned.
Ze test conceptSupplyOrigin
Ze concept: external loop at origin or by approved enquiry/measurement. Verify the current method and safety controls.
Zs test conceptCULoad
Zs concept: full earth fault loop path at a point on a circuit. Device data and current guidance determine interpretation.
RCD test conceptMFTRCDdevice response
RCD concept: functional/protective device behaviour check, with device type and test conditions verified against current guidance.
Coding decision tree conceptObservationDanger present?Potential danger?Improvement?C1C2 / FI if unresolvedC3 / note
Coding requires context and engineering judgement. Use current model forms and current BPG4/GN3 guidance for exact wording and outcome rules.
Code/termMeaningOutcome note
C1Danger present, risk of injury.Immediate remedial action required; affects overall assessment.
C2Potentially dangerous.Urgent remedial action required; affects overall assessment.
C3Improvement recommended.Advisory; normally does not make the report unsatisfactory by itself.
FIFurther investigation advised/required where risk cannot be resolved from the inspection.Check current model forms and guidance for exact wording and outcome treatment.
LIMAgreed limitation.Must be recorded honestly and not used to hide poor inspection quality.
N/V or N/ANot verified or not applicable where the form/software supports it.Use consistently with the form and agreed extent.
ObservationLook forWhy it mattersLikely rangeContext affectsRemedial directionCheck note
No RCD for sockets likely to supply outdoor equipmentSocket circuits used for portable outdoor equipment.Additional shock protection risk.C2 often cited by BPG4 examples.Socket use, labels, location, circuit arrangement.Add appropriate RCD/RCBO protection where required.Verify current BS 7671 and BPG4.
No RCD for bathroom circuits/socketBathroom circuits or accessories requiring additional protection.Increased shock risk in special locations.C2 context commonly cited.Equipment type, location, age, supplementary bonding, current requirements.Provide compliant protection/remedial design.Verify Section 701/current guidance.
Missing main bondingGas, water, oil or other extraneous services not effectively bonded where required.Dangerous potential differences.C2 commonly cited.Whether service is extraneous, supply type, continuity evidence.Install/verify suitable main protective bonding.Verify against current BS 7671.
Undersized or ineffective bondingBonding present but unsuitable, damaged or not continuous.Protective measure may be ineffective.C2/C3 context-dependent.Actual size, continuity, supply type and risk.Upgrade or repair bonding as required.Do not guess sizes from memory.
Exposed live parts / damaged accessoryBroken accessories, missing covers, exposed conductors.Immediate shock/burn risk.C1 where live parts accessible.Accessibility and energised condition.Make safe immediately, then repair/replace.BPG4 gives strong examples.
Missing consumer-unit blankOpen way or missing device with accessible live parts.Direct access to live parts.C1 where accessible live parts exist.Accessibility, enclosure condition, live state.Fit correct blank/device and verify enclosure integrity.BPG4 gives strong examples.
Burnt or overheated equipmentDiscolouration, smell, melted insulation, heat damage.Fire risk or loose/overloaded connection.C2/FI/C1 depending danger.Severity, access to live parts, active overheating.Investigate, isolate if dangerous, repair.Use competent judgement.
Broken ring final continuityOpen r1, rn or r2, inconsistent readings or test evidence.Load distribution and protective path risk.C2 often cited.Which conductor, load, protection, spur arrangements.Trace and repair ring continuity.Verify current BPG4/GN3.
Reversed polarityLine/neutral reversal at accessories or supply points.Switching/protection may not be in line conductor.C2 commonly likely.Location, device type, exposure risk.Correct polarity and retest.Verify before coding.
No CPC on lighting circuitOlder lighting circuit with no protective conductor.Class I fittings/accessories may become dangerous.C2 where Class I equipment or metal plates depend on CPC.Actual accessories, labels, RCD, user risk.Replace Class I fittings, rewire, or design suitable remedial work.BPG4 gives specific examples.
Borrowed or shared neutralUnexpected neutral paths, RCD trips, two-circuit interaction.Danger during isolation and device operation issues.C2 commonly cited.Which circuits, protective devices, isolation risk.Separate/rewire circuits correctly.Competent investigation required.
High Zs without suitable supportLoop impedance not supporting device operation.Automatic disconnection may not occur as intended.C2 context commonly cited.Device data, RCD support, supply type, measurement method.Improve fault path/protection after design review.Verify current tables/device data.
Low insulation resistanceIR result or symptoms suggesting damaged insulation.Shock/fire/unreliable operation risk.FI/C2 context-dependent.Circuit type, equipment connected, moisture, trend.Investigate and repair damaged circuit/equipment.Verify current guidance and limitations.
Plastic consumer unitPlastic enclosure, especially under stairs/escape routes.Fire containment concern, but not automatically a fail.C3 in common BPG4-type scenarios.Location, condition, damage, overheating, escape route.Recommend improvement where appropriate.Do not code solely because it is plastic.
SPD absenceNo surge protection where current rules/risk indicate it.Equipment damage and safety/service continuity risk.C3/observation commonly context-dependent.Installation type, risk assessment, client requirement, current BS 7671.Assess and install SPD where required/recommended.Verify current A4 wording.
AFDD absenceNo AFDD in categories where current rules recommend/require.Arc-fault fire risk reduction in specific premises.C3 or observation context-dependent.Premises type, circuit type, current BS 7671 category.Recommend/install where applicable.Verify current A4 wording.
EV charger on PME with unmet requirementsEV supply lacking required open-PEN/earthing safeguards.Potential touch-voltage risk in open-PEN conditions.C3/C2/FI context-dependent.Charger design, protection, supply type, manufacturer data.Review EV earthing/protection design.Verify current BS 7671 and manufacturer data.
Inadequate labels or circuit IDMissing schedules, unclear circuit labels, no RCD notices where relevant.Future isolation/testing risk.C3/observation usually.Severity, occupancy, emergency use and risk.Update labels and schedules.Use form guidance and judgement.

Example only: a typical occupied house with one consumer unit, socket ring final, lighting circuits, cooker circuit, shower circuit, boiler controls, outdoor light/socket and detached garage. No fake measurements are provided.

Example observations

  • consumer unit schedule incomplete
  • one damaged socket in kitchen
  • lighting circuit with mixed older colours
  • garage supply needs limitation due no access to buried route

Example limitation

Loft areas partly boarded and stored items restricted access; concealed cable routes not fully inspected. Limitation agreed before inspection and recorded.

Example report wording

"Kitchen double socket adjacent to worktop damaged, exposing internal parts when plug removed. Immediate repair/replacement required. Classification subject to condition found at inspection."

Example outcome

Overall outcome follows the highest-risk observations and current model-form guidance. C1/C2 or unresolved FI normally drive unsatisfactory; C3-only observations normally remain advisory.

Observation to report outcome flowObservationCodeEvidenceOutcomeNext date
Report flow: observation, schedule reference, code, evidence, summary/outcome and next inspection date.
Form areaRevision note
Client and addressIdentify person ordering report and installation address accurately.
Reason, extent and limitationsRecord why the report is needed and what was/was not covered.
Supply, earthing and bondingRecord characteristics, protective conductors and bonding details.
SchedulesInspection schedule, circuit details and test results accompany the report.
Observations and codesWrite concise, defensible observations with location, issue, risk, code and action direction.
Declaration and next dateAuthorisation, summary and recommended next inspection date should reflect findings.
Certificate boundary
Remedial work is certified using the appropriate certificate/report for that work. Do not misuse an EICR as a certificate for new installation work.

Limitations can be agreed before the inspection or arise operationally on site. They must be honest, specific and defensible, and must not be used to hide poor inspection quality.

LimitationGood wordingPoor wording
No loft accessLoft hatch blocked by stored items; roof-space wiring not fully inspected.Could not check upstairs.
No power interruptionClient refused isolation of freezer/IT circuit; dead/live tests limited and recorded.Testing not done.
Sensitive equipmentEquipment could not be disconnected; IR test limitation recorded for affected circuit.Skipped IR.
Sealed DNO equipmentDistributor equipment visually inspected only; defects referred appropriately.Supply looks fine.

No-CPC lighting

Code depends on Class I fittings/accessories, user risk, labels and remedial practicality. Verify current BPG4.

Old colours / rewireable fuses

Age is not automatically unsatisfactory. Condition, protection, labels, damage and risk drive observations.

TT systems

RCD dependence, electrode condition, bonding and test evidence need careful competent review.

EV, PV and batteries

Multiple supplies, isolators, DC risks, open-PEN and manufacturer data must be considered.

HMO/private rented

NI private tenancy and HMO licensing contexts can add duties beyond a normal homeowner EICR.

Commercial/three-phase/agricultural

Use this as awareness only; specialist competence and additional standards/procedures may be required.

Before you touch anything

  • know who is supervising you
  • understand the isolation plan
  • ask before removing covers
  • never assume a circuit is dead

Watch the supervisor

  • how scope/limitations are agreed
  • how visual observations are written
  • how test equipment is proved
  • how codes are justified

Useful questions

  • What risk makes this code appropriate?
  • What source would you check?
  • What limitation should be recorded?
  • What remedial certificate would follow?

Common mistakes

  • copying old codes without context
  • messy circuit IDs
  • forgetting limitations
  • treating live tests casually
TermApprentice recap
ExtentWhat the inspection covers.
LimitationWhat was agreed or could not be inspected/tested.
ObservationA recorded issue with location, risk and classification.
ScheduleInspection or test-result record attached to the report.
FIFurther investigation where risk cannot be resolved from available evidence.

All diagrams are original conceptual revision visuals. They are not copied from BS 7671, GN3 or proprietary guides, and they do not show terminal-level instructions.

lighting CPC continuity concept
Lighting circuit CPC continuity concept.
ZoneNearOut
Simplified bathroom zones concept. Verify current Section 701 before using any zone decision.
cover, blanks, labels, heat, device suitability
Consumer-unit inspection map: visual condition and documentation checks only.
METPipe
Main bonding concept.
IssueCodeResult
Observation-to-outcome report flow.

IET BS 7671 update page

Use for current edition and transition status. Open source

IET A4 EICR model forms

Use for current form structure, schedules and coding wording. Open source

IET Guidance Note 3

Use as the main inspection-and-testing guidance publication; check errata and current edition. Open errata

Electrical Safety First BPG4

Use the latest public coding guide as practical support, verified here as Issue 7.2. Open source

Electrical Safety First BPG2

Use for safe-isolation procedure context and industry-agreed safe working reminders. Open source

DfC NI private tenancy guidance

Use for Northern Ireland landlord dates, report duties and remedial/further-investigation timing. Open source

HSE GS38 and HSENI

Use for test-equipment and competence/safe-working context. Open GS38

HSENI electrical safety

Use for Northern Ireland workplace competence, isolation and testing context. Open source

Bathrooms and special locations
Bathrooms and shower rooms have increased electric shock risk because of water and reduced body resistance.
  • zones concept
  • IP rating concept
  • equipment suitability
  • SELV where relevant
  • electric shower risks
  • towel rails and underfloor heating
  • extractor fans
  • shaver supplies
  • supplementary bonding considerations
  • RCD/RCBO additional protection
  • manufacturer instructions
Outdoor supplies and outbuildings
Outdoor electrical work needs attention to mechanical protection, environment, water ingress, earthing, bonding and future loading.
  • SWA concept
  • buried route considerations
  • IP ratings
  • glands/earthing continuity concept
  • detached garage/shed supplies
  • TT vs PME design dependency
  • extraneous-conductive-parts
  • outdoor sockets
  • garden lighting
  • workshops
No blanket rules
Do not use blanket rules about TT or PME for every outbuilding. The correct arrangement is design-dependent.
EV charging revision notes
EV chargers introduce high continuous load and specific earthing/open-PEN considerations.
Assessment
Load and supply
Maximum demand, supply capacity and circuit route.
Earthing
Open-PEN / PME
Specific risks and protection concepts.
Protection
RCD and device data
Device/application/current standard dependent.
NI
NIE notification
NIE Networks must be notified of an EV charge point installation.
Smoke, heat and carbon monoxide alarms
Northern Ireland private rented properties have specific alarm duties.
Private tenancy dates
Alarm requirements apply to new private tenancies granted on or after 1 September 2024. Existing tenancies granted before that date had to comply by 1 December 2024.
  • smoke alarm in the room most frequently used for general daytime living
  • smoke alarm in every circulation space such as halls, stairs, landings and corridors
  • heat alarm in every kitchen
  • carbon monoxide alarm in any room or circulation space containing a flue or fixed combustion appliance as described in DfC guidance
  • smoke and heat alarms must be interlinked in private rented properties
  • hardwired alarms must be fitted by a qualified electrician
Northern Ireland compliance recap
NI has its own domestic electrical compliance context. Do not import England/Wales assumptions.
Correction
Part P
NI does not use the same domestic electrical Part P system as England and Wales.
Domestic work
No direct Part P equivalent
Work still needs safe design, installation, inspection and testing.
Correction
Technical Booklet P
It relates to sanitary appliances, unvented hot water and scalding risk.
Workplace
HSENI context
Competence, isolation/testing and appropriate standards remain relevant.
NI private tenancy electrical safety checks
Private landlords in Northern Ireland must arrange periodic inspection and testing by a qualified person.
ItemRecap
IntervalAt least every 5 years, or sooner if the report requires it.
New tenanciesNew private tenancies granted on or after 1 April 2025 must comply from that date.
Existing tenanciesExisting tenancies granted before 1 April 2025 must comply by 1 December 2025.
Inspection scopeFixed wiring, socket-outlets, light fittings, consumer units and permanently connected equipment such as showers and extractor fans.
Report dutiesLandlords must obtain, retain and provide reports where required and arrange required remedial work or further investigation.
Source library
Official/current source links used as review anchors.
SourceUsed forLink
IET BS 7671 current edition/amendmentEdition and amendment status.Open source
Electrical Safety First NI Building RegulationsNI domestic electrical Building Regulations context.Open source
Department of Finance NI Technical Booklet PTechnical Booklet P correction.Open source
DfC NI private tenancy electrical safetyPrivate-tenancy electrical safety dates, scope and duties.Open source
DfC NI smoke, heat and CO alarmsPrivate-tenancy alarm dates and requirements.Open source
HSENI electrical safetyWorkplace competence and safety context.Open source
Consumer Council NI EV chargingEV charging and NIE Networks notification context.Open source
NIE Networks EVs / Heat PumpsLow carbon technologies application and notification process checks.Open source
Manual review checklist
Sections that need qualified/current-standard review before being relied upon.
  • BS 7671 edition/amendment note
  • safe isolation wording
  • inspection and testing wording
  • EICR coding notes
  • consumer unit/protective device notes
  • SPDs and AFDDs
  • bathroom and special-location notes
  • EV charging/open-PEN/PME notes
  • outbuilding earthing and bonding notes
  • NI private tenancy electrical safety dates and duties
  • NI smoke, heat and CO alarm dates and duties
  • Building Control and NI compliance wording

Sources & Review Status

Draft Technical review required
This app is a competent-person revision resource. It should be checked against the current edition of BS 7671, official Northern Ireland sources, employer procedures and competent electrical judgement before being relied upon.
Scope Revision, not replacement
The notes support recap of principles, terminology, tests and compliance context. They do not replace design, installation, inspection, testing, certification, supervision or formal training.
Official source anchors
  • IET BS 7671 current edition/amendment
  • Electrical Safety First - Building Regulations in Northern Ireland
  • Department of Finance NI - Technical Booklet P
  • Department for Communities NI - private tenancy electrical safety
  • Department for Communities NI - smoke, heat and CO alarms
  • HSENI electrical safety
  • Consumer Council NI - EV charging
  • NIE Networks low carbon technologies
  • BS 7671 edition/amendment note reviewed
  • safe isolation wording reviewed
  • inspection/testing wording reviewed
  • NI tenancy and alarm dates reviewed
  • EV/open-PEN/PME wording reviewed
  • special location and outbuilding notes reviewed