| Area | Review source | Why |
|---|---|---|
| BS 7671 | IET/BSI current edition information | Edition and amendment references can change. |
| NI domestic compliance | Electrical Safety First and official NI sources | Do not import England/Wales Part P assumptions into NI. |
| Private tenancy duties | Department for Communities NI | Dates, report duties and alarm requirements are legal/current-state content. |
| EV charging | Consumer Council NI and NIE Networks | Notification and network process wording can change. |
BS 7671 is updated by amendments. As of 2026, BS 7671:2018+A4:2026 has been published. During the transition period, the previous edition remains valid until 15 October 2026. After transition, check the latest IET/BSI position before relying on edition wording.
| Principle | Revision note |
|---|---|
| Identify | Confirm the correct circuit/equipment. Labels and colours are not enough. |
| Isolate | Consider all relevant live conductors, supplies and alternative sources. |
| Secure | Prevent re-energisation using lock-off/warning methods where appropriate. |
| Prove dead | Test at the point of work with suitable equipment and procedure. |
| Term | Meaning |
|---|---|
| BS 7671 | UK standard for electrical installations, published with amendments. |
| Competent/skilled person | Person with sufficient knowledge, training, experience and judgement for the task and risk. |
| Line / neutral / CPC | Line is live conductor, neutral is return conductor, CPC is circuit protective conductor. |
| MET | Main earthing terminal for earthing, bonding and protective conductors as applicable. |
| ADS | Automatic disconnection of supply under required fault conditions. |
| RCD / RCCB / RCBO | Residual current devices; RCBO combines residual current and overcurrent protection. |
| MCB / SPD / AFDD | Overcurrent device, surge protective device and arc fault detection device. |
| Zs / Ze / R1+R2 | Earth fault loop impedance terms used in fault path and verification work. |
| EIC / MEIWC / EICR | Installation certificate, minor works certificate and condition report. |
| PME / TN-S / TN-C-S / TT | Supply earthing concepts. Confirm the actual arrangement on site. |
Lighting circuits may contain permanent line, switched line, neutral and CPC conductors depending on wiring method. Older installations, alterations and different methods can make conductor identification unreliable by colour alone.
- permanent line and switched line
- neutral at switch vs neutral at light
- CPC continuity
- borrowed/shared neutrals risk
- two-way/intermediate switching concept
- smart controls and neutral requirement
- SELV/driver considerations for LED lighting
Socket-outlet circuits may be radial or ring final circuits. The arrangement, protective device, cable route, loading, RCD/RCBO protection and test results must all be considered.
- radial concept
- ring final concept
- unfused spur concept
- fused connection unit concept
- load distribution
- continuity of line, neutral and CPC
- ring final testing purpose
- limitations of visual inspection alone
High-load or fixed equipment circuits require design around the actual load, manufacturer instructions, cable route, installation method, grouping, thermal insulation, voltage drop, protection, isolation and certification.
- cooker, hob or oven
- electric shower
- immersion heater
- EV charger
- heat pump
- outbuilding supply
- workshop equipment
| Selection factor | Revision note |
|---|---|
| Design current and future load | Know the actual load and realistic use case. |
| Installation method and grouping | Heat dissipation affects usable capacity. |
| Voltage drop and Zs | Length and impedance affect performance and disconnection. |
| Mechanical/environmental conditions | Route, protection and surroundings matter. |
| Manufacturer instructions | Equipment requirements are part of design context. |
| Supply type | Basic concept | Cautions |
|---|---|---|
| TN-S | Separate supply neutral and earth paths from source. | Confirm actual supply; do not assume from appearance. |
| TN-C-S / PME | Neutral and earth combined in part of supply, separated at installation. | EV, outbuildings and special cases need care. |
| TT | Installation uses local earth electrode for earthing. | Electrode resistance, RCDs, testing and maintenance matter. |
- cooker, hob and oven loads
- washing machine, dryer and dishwasher loads
- boiler and controls
- extraction and lighting
- boiling-water taps
- dedicated circuits vs shared circuits
- isolation and accessibility
- manufacturer instructions
| Document | Used for | Revision notes |
|---|---|---|
| EIC | New installation, rewire, new circuits or significant work. | Records design, construction, inspection and testing responsibility. |
| MEIWC | Certain minor additions or alterations without a new circuit. | Not for every job; check scope. |
| EICR | Condition report for an existing installation. | Records observations, codes and overall assessment; not a certificate for new work. |
| Code | Meaning | Revision note |
|---|---|---|
| C1 | Danger present. | Immediate action required. |
| C2 | Potentially dangerous. | Urgent remedial action required. |
| C3 | Improvement recommended. | Not normally unsatisfactory by itself. |
| FI | Further investigation required. | Needs investigation without delay. |
| LIM | Limitation. | Agreed limitation; must not hide accessible defects. |
Competent-person reference only. This section is for electrical learning, revision and professional reference. It is not a substitute for BS 7671, IET Guidance Note 3, manufacturer instructions, risk assessment, safe systems of work, insurance conditions or competent supervision.
Apprentice note. If you are in training, do not carry out EICR work unsupervised unless you are competent and authorised to do so. Use this section to understand the process, terminology, observations and report structure, then verify everything against current standards and supervisor instructions.
Regulation note. Standards, model forms and legal duties can change. Verify current requirements against the applicable version of BS 7671, current IET guidance, Electrical Safety First guidance, current Northern Ireland Department for Communities guidance, manufacturer information and local procedures.
An Electrical Installation Condition Report records the condition of an existing electrical installation within agreed extent and limitations. It is a structured inspection and testing report, not a design certificate for new work and not a quote for remedial work.
What it is
A report on whether an existing installation is satisfactory for continued service, based on inspection, testing, observations, limitations and competent judgement.
What it is not
It is not an Electrical Installation Certificate, not a Minor Works Certificate, not a consumer-unit replacement certificate and not proof that future alterations are safe.
Who carries it out
A competent and authorised person with suitable inspection/testing knowledge, experience, equipment, calibration arrangements, insurance and safe systems of work.
Old installations
Older work is assessed against current safety expectations, but age alone does not make an installation unsafe. Coding depends on risk, condition and context.
| Document | Purpose | Typical use |
|---|---|---|
| EICR | Condition report for an existing installation. | Periodic inspection, landlord checks, sale/purchase condition review, workplace maintenance. |
| EIC | Certificate for new installation work. | New installation, rewire, new circuit or major alteration requiring design/construction verification. |
| MEIWC | Certificate for certain minor electrical installation work. | Limited additions or alterations where no new circuit is installed and the certificate scope is appropriate. |
Northern Ireland
NI does not operate the same domestic Part P notification system used in England and Wales. Other duties can still apply, including private-tenancy, HMO, workplace, fire, building and contractual duties.
BS 7671
BS 7671:2018+A4:2026 has been published and is in transition. Confirm which edition/amendment the report is based on before relying on wording or model-form interpretation.
Guidance Note 3
GN3 is the main inspection-and-testing guidance book. It is paid material, so this site summarises principles in original wording and points readers to the official publication.
BPG4
Electrical Safety First Best Practice Guide 4 is a public practical coding aid for domestic and similar installations. Use the latest public BPG4, verified during implementation as Issue 7.2, and cross-check current forms.
Frequency and reports
NI private-tenancy reports are normally required at least every 5 years. Copy, retention, council-request and remedial-work timings should be checked against current DfC guidance.
Guidance not law
This section is revision guidance only. It does not replace the standard, GN3, competent-person judgement, scheme guidance, employer procedures or legal advice.
Client questions
- reason for report and property use
- previous EIC/EICR/MEIWC availability
- known faults or nuisance tripping
- whether power can be interrupted
Installation clues
- property age and occupancy
- number of consumer units or DBs
- likely supply/earthing type
- outbuildings and external supplies
Special systems
- PV, battery storage, generators or UPS
- EV charging
- immersion, shower, cooker and heating
- alarms, data, security and ELV systems
Occupied property risk
- vulnerable persons and medical equipment
- fridges, freezers, IT equipment and alarms
- pets and access to rooms, lofts or garages
- tenant/landlord communication route
Core test kit
Multifunction tester, proving unit, two-pole voltage indicator or approved test lamp, GS38-compliant leads/probes, continuity leads and long lead/wander lead where appropriate.
Support kit
Lock-off kit, warning notices, labels, camera, notebook, forms/software, suitable hand tools, PPE and torque screwdriver where relevant.
Condition and calibration
Check instrument condition, lead condition, battery state, calibration status and suitability for the installation category before use.
Socket tester warning
Plug-in socket testers can indicate some issues but do not replace competent inspection, testing, safe isolation or calibrated instruments.
Do not rely on neon screwdrivers, assumptions, labels, conductor colours or non-contact indicators as the primary method of proving dead. Watch for borrowed neutrals, multiple supplies, PV, battery storage, generators, UPS, heating/control circuits, smart controls, automatic switching and diverted neutral currents.
Intake and supply
- service head, metering and isolator visual condition
- main switch and tails visible condition
- earthing arrangement indicators
- supplier/distributor defects referred appropriately
Consumer unit
- covers, blanks, barriers and IP suitability
- signs of overheating, damage or loose equipment
- RCD/RCBO/SPD/AFDD presence where relevant
- accessibility, schedules and labels
Earthing and bonding
- main earthing conductor and MET
- main protective bonding to gas, water, oil, steel or other services where relevant
- continuity and connection condition
- extraneous-conductive-parts judgement
Circuits and accessories
- cable condition, support and mechanical protection
- safe zone awareness and damage signs
- sockets, switches, accessories and evidence of poor alterations
- lighting, downlights, showers, cookers, heating and outdoor equipment
| Type | Revision effect | EICR caution |
|---|---|---|
| TN-S | Separate supply neutral and earth paths. | Confirm by inspection/enquiry/testing; appearance alone can mislead. |
| TN-C-S / PME | Combined supply conductor separated at the installation. | Open-PEN risk awareness for EV, outbuildings and outdoor conductive parts. |
| TT | Local electrode provides installation earth reference. | RCD effectiveness, electrode condition and bonding require careful review. |
| IT | Rare/special arrangement. | Do not assume domestic TN/TT logic applies; check specialist design information. |
Ring finals
Inspect accessories, spurs, load signs and continuity evidence. Common issues include broken ring conductors, borrowed/shared neutrals, damaged accessories and poor additions.
Radial sockets
Review route, load, RCD/RCBO protection, CPC continuity, polarity and outdoor-use implications.
Lighting
Check CPC presence, Class I fittings, downlight heat/fire issues, borrowed neutrals, switching and older colours.
High-load circuits
Cookers, showers, immersion heaters and heating circuits need review against load, isolation, route, protection and manufacturer data.
External/outbuilding
Consider mechanical protection, water ingress, glands, earthing/bonding, extraneous parts, future loads and PME/TT decisions.
Special interfaces
EV, PV, batteries, smoke/heat alarms and ELV/data separation need system-specific awareness and source checks.
Dead tests establish continuity, insulation condition, polarity foundations, circuit identity and protective conductor presence without energising test points. They are not a substitute for competence, calibrated equipment or current GN3/BS 7671 instructions.
| Dead test purpose | What it establishes | Common traps |
|---|---|---|
| CPC/bonding continuity | Protective path and bonding connection continuity. | Parallel paths, poor contact, wrong conductor or inaccessible points. |
| Ring final r1/rn/r2 | Continuity of line, neutral and CPC around the ring. | Cross-connections, spurs mistaken for ring legs, loose terminals. |
| R1+R2 | Line-to-CPC continuity contribution to fault path. | Borrowed neutrals, open CPCs, parallel earth paths. |
| Insulation resistance | Condition between conductors and circuits. | Sensitive equipment, connected loads, SPDs, electronics and damp conditions. |
| Dead polarity | Line conductor switching/protection and conductor identification. | Assumptions from colour, older wiring and mixed-age alterations. |
| Live test | Purpose | Risk/limitation |
|---|---|---|
| Ze | External earth fault loop impedance at origin or by enquiry/measurement as appropriate. | Requires care around supply equipment and live conditions; verify current method. |
| PFC/PEFC/PSCC | Prospective fault current values for breaking-capacity assessment. | Supply conditions and measurement method affect result. |
| Zs | Earth fault loop impedance at circuit points for disconnection assessment. | No-trip tests have limitations; RCD support needs current guidance. |
| RCD/RCBO checks | Confirms residual-current device function against relevant requirements. | Type AC/A/F/B awareness, load effects and manufacturer data matter. |
| Functional/voltage/polarity | Confirms operation, voltage presence and line/neutral arrangement. | Can expose users and equipment to risk if poorly planned. |
| Code/term | Meaning | Outcome note |
|---|---|---|
| C1 | Danger present, risk of injury. | Immediate remedial action required; affects overall assessment. |
| C2 | Potentially dangerous. | Urgent remedial action required; affects overall assessment. |
| C3 | Improvement recommended. | Advisory; normally does not make the report unsatisfactory by itself. |
| FI | Further investigation advised/required where risk cannot be resolved from the inspection. | Check current model forms and guidance for exact wording and outcome treatment. |
| LIM | Agreed limitation. | Must be recorded honestly and not used to hide poor inspection quality. |
| N/V or N/A | Not verified or not applicable where the form/software supports it. | Use consistently with the form and agreed extent. |
| Observation | Look for | Why it matters | Likely range | Context affects | Remedial direction | Check note |
|---|---|---|---|---|---|---|
| No RCD for sockets likely to supply outdoor equipment | Socket circuits used for portable outdoor equipment. | Additional shock protection risk. | C2 often cited by BPG4 examples. | Socket use, labels, location, circuit arrangement. | Add appropriate RCD/RCBO protection where required. | Verify current BS 7671 and BPG4. |
| No RCD for bathroom circuits/socket | Bathroom circuits or accessories requiring additional protection. | Increased shock risk in special locations. | C2 context commonly cited. | Equipment type, location, age, supplementary bonding, current requirements. | Provide compliant protection/remedial design. | Verify Section 701/current guidance. |
| Missing main bonding | Gas, water, oil or other extraneous services not effectively bonded where required. | Dangerous potential differences. | C2 commonly cited. | Whether service is extraneous, supply type, continuity evidence. | Install/verify suitable main protective bonding. | Verify against current BS 7671. |
| Undersized or ineffective bonding | Bonding present but unsuitable, damaged or not continuous. | Protective measure may be ineffective. | C2/C3 context-dependent. | Actual size, continuity, supply type and risk. | Upgrade or repair bonding as required. | Do not guess sizes from memory. |
| Exposed live parts / damaged accessory | Broken accessories, missing covers, exposed conductors. | Immediate shock/burn risk. | C1 where live parts accessible. | Accessibility and energised condition. | Make safe immediately, then repair/replace. | BPG4 gives strong examples. |
| Missing consumer-unit blank | Open way or missing device with accessible live parts. | Direct access to live parts. | C1 where accessible live parts exist. | Accessibility, enclosure condition, live state. | Fit correct blank/device and verify enclosure integrity. | BPG4 gives strong examples. |
| Burnt or overheated equipment | Discolouration, smell, melted insulation, heat damage. | Fire risk or loose/overloaded connection. | C2/FI/C1 depending danger. | Severity, access to live parts, active overheating. | Investigate, isolate if dangerous, repair. | Use competent judgement. |
| Broken ring final continuity | Open r1, rn or r2, inconsistent readings or test evidence. | Load distribution and protective path risk. | C2 often cited. | Which conductor, load, protection, spur arrangements. | Trace and repair ring continuity. | Verify current BPG4/GN3. |
| Reversed polarity | Line/neutral reversal at accessories or supply points. | Switching/protection may not be in line conductor. | C2 commonly likely. | Location, device type, exposure risk. | Correct polarity and retest. | Verify before coding. |
| No CPC on lighting circuit | Older lighting circuit with no protective conductor. | Class I fittings/accessories may become dangerous. | C2 where Class I equipment or metal plates depend on CPC. | Actual accessories, labels, RCD, user risk. | Replace Class I fittings, rewire, or design suitable remedial work. | BPG4 gives specific examples. |
| Borrowed or shared neutral | Unexpected neutral paths, RCD trips, two-circuit interaction. | Danger during isolation and device operation issues. | C2 commonly cited. | Which circuits, protective devices, isolation risk. | Separate/rewire circuits correctly. | Competent investigation required. |
| High Zs without suitable support | Loop impedance not supporting device operation. | Automatic disconnection may not occur as intended. | C2 context commonly cited. | Device data, RCD support, supply type, measurement method. | Improve fault path/protection after design review. | Verify current tables/device data. |
| Low insulation resistance | IR result or symptoms suggesting damaged insulation. | Shock/fire/unreliable operation risk. | FI/C2 context-dependent. | Circuit type, equipment connected, moisture, trend. | Investigate and repair damaged circuit/equipment. | Verify current guidance and limitations. |
| Plastic consumer unit | Plastic enclosure, especially under stairs/escape routes. | Fire containment concern, but not automatically a fail. | C3 in common BPG4-type scenarios. | Location, condition, damage, overheating, escape route. | Recommend improvement where appropriate. | Do not code solely because it is plastic. |
| SPD absence | No surge protection where current rules/risk indicate it. | Equipment damage and safety/service continuity risk. | C3/observation commonly context-dependent. | Installation type, risk assessment, client requirement, current BS 7671. | Assess and install SPD where required/recommended. | Verify current A4 wording. |
| AFDD absence | No AFDD in categories where current rules recommend/require. | Arc-fault fire risk reduction in specific premises. | C3 or observation context-dependent. | Premises type, circuit type, current BS 7671 category. | Recommend/install where applicable. | Verify current A4 wording. |
| EV charger on PME with unmet requirements | EV supply lacking required open-PEN/earthing safeguards. | Potential touch-voltage risk in open-PEN conditions. | C3/C2/FI context-dependent. | Charger design, protection, supply type, manufacturer data. | Review EV earthing/protection design. | Verify current BS 7671 and manufacturer data. |
| Inadequate labels or circuit ID | Missing schedules, unclear circuit labels, no RCD notices where relevant. | Future isolation/testing risk. | C3/observation usually. | Severity, occupancy, emergency use and risk. | Update labels and schedules. | Use form guidance and judgement. |
Example only: a typical occupied house with one consumer unit, socket ring final, lighting circuits, cooker circuit, shower circuit, boiler controls, outdoor light/socket and detached garage. No fake measurements are provided.
Example observations
- consumer unit schedule incomplete
- one damaged socket in kitchen
- lighting circuit with mixed older colours
- garage supply needs limitation due no access to buried route
Example limitation
Loft areas partly boarded and stored items restricted access; concealed cable routes not fully inspected. Limitation agreed before inspection and recorded.
Example report wording
"Kitchen double socket adjacent to worktop damaged, exposing internal parts when plug removed. Immediate repair/replacement required. Classification subject to condition found at inspection."
Example outcome
Overall outcome follows the highest-risk observations and current model-form guidance. C1/C2 or unresolved FI normally drive unsatisfactory; C3-only observations normally remain advisory.
| Form area | Revision note |
|---|---|
| Client and address | Identify person ordering report and installation address accurately. |
| Reason, extent and limitations | Record why the report is needed and what was/was not covered. |
| Supply, earthing and bonding | Record characteristics, protective conductors and bonding details. |
| Schedules | Inspection schedule, circuit details and test results accompany the report. |
| Observations and codes | Write concise, defensible observations with location, issue, risk, code and action direction. |
| Declaration and next date | Authorisation, summary and recommended next inspection date should reflect findings. |
Limitations can be agreed before the inspection or arise operationally on site. They must be honest, specific and defensible, and must not be used to hide poor inspection quality.
| Limitation | Good wording | Poor wording |
|---|---|---|
| No loft access | Loft hatch blocked by stored items; roof-space wiring not fully inspected. | Could not check upstairs. |
| No power interruption | Client refused isolation of freezer/IT circuit; dead/live tests limited and recorded. | Testing not done. |
| Sensitive equipment | Equipment could not be disconnected; IR test limitation recorded for affected circuit. | Skipped IR. |
| Sealed DNO equipment | Distributor equipment visually inspected only; defects referred appropriately. | Supply looks fine. |
No-CPC lighting
Code depends on Class I fittings/accessories, user risk, labels and remedial practicality. Verify current BPG4.
Old colours / rewireable fuses
Age is not automatically unsatisfactory. Condition, protection, labels, damage and risk drive observations.
TT systems
RCD dependence, electrode condition, bonding and test evidence need careful competent review.
EV, PV and batteries
Multiple supplies, isolators, DC risks, open-PEN and manufacturer data must be considered.
HMO/private rented
NI private tenancy and HMO licensing contexts can add duties beyond a normal homeowner EICR.
Commercial/three-phase/agricultural
Use this as awareness only; specialist competence and additional standards/procedures may be required.
Before you touch anything
- know who is supervising you
- understand the isolation plan
- ask before removing covers
- never assume a circuit is dead
Watch the supervisor
- how scope/limitations are agreed
- how visual observations are written
- how test equipment is proved
- how codes are justified
Useful questions
- What risk makes this code appropriate?
- What source would you check?
- What limitation should be recorded?
- What remedial certificate would follow?
Common mistakes
- copying old codes without context
- messy circuit IDs
- forgetting limitations
- treating live tests casually
| Term | Apprentice recap |
|---|---|
| Extent | What the inspection covers. |
| Limitation | What was agreed or could not be inspected/tested. |
| Observation | A recorded issue with location, risk and classification. |
| Schedule | Inspection or test-result record attached to the report. |
| FI | Further investigation where risk cannot be resolved from available evidence. |
All diagrams are original conceptual revision visuals. They are not copied from BS 7671, GN3 or proprietary guides, and they do not show terminal-level instructions.
Pre-visit
- reason for report
- previous paperwork requested
- access and power interruption agreed
- special systems identified
Tools
- MFT and proving unit
- voltage indicator
- lock-off kit
- leads/probes checked
Safe isolation
- identify circuit
- inform occupants
- secure isolation
- prove/test/re-prove
Visual inspection
- intake visual check
- consumer unit condition
- earthing and bonding
- accessories and external equipment
Dead testing
- CPC/bonding continuity
- ring final continuity
- R1+R2
- insulation resistance precautions
Live testing
- risk assessment
- Ze/Zs/PFC purpose
- RCD/RCBO checks
- functional checks
Coding
- risk identified
- code justified
- source checked
- urgent danger communicated
Report completion
- extent and limitations complete
- schedules attached
- observations defensible
- next inspection date set
Apprentice day
- supervisor identified
- do not work unsupervised
- record neatly
- ask before touching
Common defects
- exposed live parts
- missing bonding
- broken ring
- polarity/RCD/Zs issues
IET BS 7671 update page
Use for current edition and transition status. Open source
IET A4 EICR model forms
Use for current form structure, schedules and coding wording. Open source
IET Guidance Note 3
Use as the main inspection-and-testing guidance publication; check errata and current edition. Open errata
Electrical Safety First BPG4
Use the latest public coding guide as practical support, verified here as Issue 7.2. Open source
Electrical Safety First BPG2
Use for safe-isolation procedure context and industry-agreed safe working reminders. Open source
DfC NI private tenancy guidance
Use for Northern Ireland landlord dates, report duties and remedial/further-investigation timing. Open source
HSE GS38 and HSENI
Use for test-equipment and competence/safe-working context. Open GS38
HSENI electrical safety
Use for Northern Ireland workplace competence, isolation and testing context. Open source
- zones concept
- IP rating concept
- equipment suitability
- SELV where relevant
- electric shower risks
- towel rails and underfloor heating
- extractor fans
- shaver supplies
- supplementary bonding considerations
- RCD/RCBO additional protection
- manufacturer instructions
- SWA concept
- buried route considerations
- IP ratings
- glands/earthing continuity concept
- detached garage/shed supplies
- TT vs PME design dependency
- extraneous-conductive-parts
- outdoor sockets
- garden lighting
- workshops
- smoke alarm in the room most frequently used for general daytime living
- smoke alarm in every circulation space such as halls, stairs, landings and corridors
- heat alarm in every kitchen
- carbon monoxide alarm in any room or circulation space containing a flue or fixed combustion appliance as described in DfC guidance
- smoke and heat alarms must be interlinked in private rented properties
- hardwired alarms must be fitted by a qualified electrician
| Item | Recap |
|---|---|
| Interval | At least every 5 years, or sooner if the report requires it. |
| New tenancies | New private tenancies granted on or after 1 April 2025 must comply from that date. |
| Existing tenancies | Existing tenancies granted before 1 April 2025 must comply by 1 December 2025. |
| Inspection scope | Fixed wiring, socket-outlets, light fittings, consumer units and permanently connected equipment such as showers and extractor fans. |
| Report duties | Landlords must obtain, retain and provide reports where required and arrange required remedial work or further investigation. |
| Source | Used for | Link |
|---|---|---|
| IET BS 7671 current edition/amendment | Edition and amendment status. | Open source |
| Electrical Safety First NI Building Regulations | NI domestic electrical Building Regulations context. | Open source |
| Department of Finance NI Technical Booklet P | Technical Booklet P correction. | Open source |
| DfC NI private tenancy electrical safety | Private-tenancy electrical safety dates, scope and duties. | Open source |
| DfC NI smoke, heat and CO alarms | Private-tenancy alarm dates and requirements. | Open source |
| HSENI electrical safety | Workplace competence and safety context. | Open source |
| Consumer Council NI EV charging | EV charging and NIE Networks notification context. | Open source |
| NIE Networks EVs / Heat Pumps | Low carbon technologies application and notification process checks. | Open source |
- BS 7671 edition/amendment note
- safe isolation wording
- inspection and testing wording
- EICR coding notes
- consumer unit/protective device notes
- SPDs and AFDDs
- bathroom and special-location notes
- EV charging/open-PEN/PME notes
- outbuilding earthing and bonding notes
- NI private tenancy electrical safety dates and duties
- NI smoke, heat and CO alarm dates and duties
- Building Control and NI compliance wording